WHO Approved Temperature monitoring device which can caters for 8 probes (4 x wired & 4 x wireless), Door monitoring, Power Failure, GPS, Ambient Temperature and Humidty
A cost effective solution to mitigate GPRS cost but uses our same robust web platform “myfridgeonline”
What else can you get from Ikhaya Automation Systems?
Ikhaya Automation Systems’ temperature monitoring solutions are our best-selling products but our expertise doesn’t end here. Our solutions can also monitor humidity, pressure, oxygen, power and door status and much more. Our clients are most excited about our recent dashboard introduction which now makes it easier than ever to view your data and align your business operation with it.
Who else works with Ikhaya Automation Systems?
“I have been working with Ikhaya for 3-4 years. We currently have approximately 100 sensors installed into our facilities across South Africa. The real-time monitoring system, supplied by Ikhaya, conforms to our requirements of monitoring our ambient temperature and humidity in the warehouses. The installed system has been validated and SANAS calibrated on an annual basis which forms part of our international quality policy.
The staff are very knowledgeable in their field and gladly assist whenever there is a question or query. This makes dealing with Ikhaya a pleasure as they meet all expectations for service delivery.” – Pieter Truter, National Facilities Manager for Johnson & Johnson Medical Devices Companies
Product Specifications
Spec | VM 1000 | WiFi Logger | TIN |
---|---|---|---|
PQS Approved | E006/61 | N | N |
Real time Monitoring | Y | Y | Y |
Web Based | Y | Y | Y |
Historical Data | Y | Y | Y |
Automated Reports | Y | Y | Y |
Graphs | Y | Y | Y |
SMS Alert | Y | Y | Y |
Email Alert | Y | Y | Y |
Buzzer Alert | Y | N | N |
LCD | Y | N | N |
Wireless Probes | Y | N | Y |
Power Failure Alert | Y | Y | Y |
Door Monitoring | Y | Y | Y |
Service Fee | Y | Y | Y |
SD Card Port | Y | N | N |
USB Download Port | Y | Y | N |
Internal Temp & Humidity | Y | Y | Y |
Range | -200 to +600°C | -30 to +55°C | -30°C to +60°C |
Wired Probes | 4 | 1 | 1 |
Wireless Probes | 4 | 0 | 1 |
Accuracy | 0.5°C | 0.5°C | 0.2°C |
General | |
Model | VM 1000 |
Dimensions | 135mm x 100mm x 50mm |
Weight | 0.45kg |
Mounting Method | Velcro/Mounting Screws |
Mode of Communication | GPRS |
Mode of Operation | Electronic |
ICASA Approval | TA-2018/2266 |
WHO Approval | PQS Code: E006/061 |
Environmental Specifications | |
Operating Temperature | 5°C to 60°C |
IP Rating | IP 54 |
Storage Temperature | 5°C to 50°C |
Electrical Specifications (Option 1) | |
Input Supply | 100 – 220Vac Adaptor with 12vdc output, 1 Amp (centre pin positive) |
Standalone Battery Backup | Yes ( Lithium – Non rechargeable) |
Current Consumption @ 12V | Active Mode (GSM Transmission active): 150mA (typical) average |
Instantaneous peak current: 0.6 – 1 Amp | |
Standby Mode: 55mA, Display ON | |
Standby Mode (Adapter): 15mA (Power Down – LCD Off) | |
Standby Mode ( Battery): 40uA | |
Battery Type | Lithium Non Rechargeable |
Battery Operating Life | 3-5 Years (LCD Display off, Power Save mode active) |
Electrical Specifications (Option 2) | |
Input Supply | Lithium Battery 3.6Vdc, 6.5Ah |
Current Consumption @ 7.2 VDC | Active Mode (Transmission): 150mA |
Standby Mode: 40uA (Display off) | |
Battery Type | Lithium Non Rechargeable |
Battery Operating Life | 3-5 Years |
Number of Batteries | 2 x C Cell Lithium |
Logging | |
Logging Interval | Default: 10 Minutes |
Minimum: 1 Minute | |
Maximum: 1440 Minutes | |
(Configurable in 1 minute step duration) | |
Standard Upload Frequency | Once per day or on alarm when in battery mode; configurable when connected to mains power |
Memory Capability | 14 000 logs internal Flash |
Alarms | |
On-board | LCD |
Internal Buzzer | |
Remote | SMS, Email, Web |
User interface | |
Viewing and Programming | WEB |
Membrane & LCD | |
Quality | |
Standard | ISO 9001-2015 |
Inputs | |
Digital Inputs | One (Door Sensor) |
Temperature Sensor | |
Digital Probes | 4 ports but up to 8 sensors in parallel (Max of 80 meters cable in total) |
Sensor Temperature Range | -30°C to +55°C |
Sensor Temperature Accuracy | ±0.5°C (-20°C to +55°C) |
Sensor Resolution | 0.0625°C steps |
Internal Temperature Humidity Sensor | |
Digital Probes | 1 |
Sensor Temperature Range | 0°C to +60°C |
Sensor Temperature Accuracy | ±0.3°C |
Sensor Humidity Range | 0% to 100% |
Sensor Humidity Accuracy | ±2% |
Interface | |
Membrane | Control Buttons |
Display | |
Type | Graphic, OLED Backlit |
Resolution | 128 x 64 Pixels |
Colour | Blue |
Display Length / Width | 65mm x 33mm |
General | ||
---|---|---|
Model | WiFi I/E-T/TH/A | |
Dimensions | 80mm x 52mm x 40mm | |
Weight | 0.1kg | |
Mounting method | Velcro/Two way tape/Hang | |
Mode of Communication | wifi | |
Mode of operation | Electronic | |
ICASA Approval | TA-2018/2266 | |
Environmental Specifications | ||
Operating Temperature | 5°C to 60°C | |
IP Rating | IP 44 | |
Storage Temperature | 5°C to 50°C | |
Electrical Specifications | ||
Power Supply | 100 – 220Vac Adaptor with 5vdc output, 500mA USB A Female | |
Cable | Male USB 2.0 A to Male Micro B USB | |
Communication | ||
Bandwidth Standard | 802.11 b/g/n | |
Range | 50m to 100m Line of sight (environment dependant) | |
Logging | ||
Logging Interval | Default: 10 Minutes Minimum: 10 Minute Maximum: 1440 Minutes (Configurable in 1 minute step duration) | |
Standard Upload Frequency | Default: 10 Minutes Minimum: 10 Minute Maximum: 1440 Minutes (Configurable in 10 minute step duration) | |
Memory capability | 80 logs internal EPROM | |
User Interface | ||
Viewing and Programming | WEB & Local PC application | |
Alarms | ||
External | SMS, Email & WEB | |
Quality | ||
Standard | ISO 9001-2015 | |
Internal Temperature Humidity Sensor | ||
Digital Probes | 1 | |
Sensor Temperature Range | -30°C to +60°C | |
Sensor Temperature Accuracy | ±0.3°C | |
Sensor Humidity Range | 0 to 100% | |
Sensor Humidity Accuracy | ±2% |
General | ||
---|---|---|
Model | TIN I/E-T/TH/P | |
Dimensions | 100mm x 100mm x 50mm | |
Weight | <0.2kg | |
Mounting method | Velcro/Two way tape/Hang | |
Mode of Communication | LORA | |
Mode of operation | Electronic | |
ICASA Approval | TA-2018/2266 | |
Environmental Specifications | ||
Operating Temperature | 5°C to 60°C | |
IP Rating | IP 56 | |
Storage Temperature | 5°C to 50°C | |
Electrical Specifications | ||
Input Supply | 4.5Vdc, 7.2Ah | |
Battery Type | Alkaline, Type C, 3S Battery Pack | |
Battery Operating Life | 1 Year | |
Communication | ||
Bandwidth Standard | 868Mhz | |
Range | 0m to 2000m Line of sight (environment dependant) | |
Logging | ||
Logging Interval |
Default: 10 Minutes Minimum: 10 Minute Maximum: 1440 Minutes (Configurable in 1 minute step duration) |
|
Standard Upload Frequency |
Default: 10 Minutes Minimum: 10 Minute Maximum: 1440 Minutes (Configurable in 10 minute step duration) |
|
Memory capability | 3 logs internal EPROM | |
User Interface | ||
Viewing and Programming | WEB www.myfridgeonline.com | |
Alarms | ||
External | WEB, SMS, Email & Telegram | |
Quality | ||
Standard | ISO 9001-2015 | |
Internal Temperature Humidity Sensor | ||
Digital Probes | 1 | |
Sensor Temperature Range | -30°C to +60°C | |
Sensor Temperature Accuracy | ±0.2°C | |
Sensor Humidity Range | 0 to 100% | |
Sensor Humidity Accuracy | ±2% |